Description

The Emerson DeltaV Distributed Control System (DCS) controllers and IO cards through 2022-04-29 misuse passwords. Access to privileged operations on the maintenance port TELNET interface (23/TCP) on M-series and SIS (CSLS/LSNB/LSNG) nodes is controlled by means of utility passwords. These passwords are generated using a deterministic, insecure algorithm using a single seed value composed of a day/hour/minute timestamp with less than 16 bits of entropy. The seed value is fed through a lookup table and a series of permutation operations resulting in three different four-character passwords corresponding to different privilege levels. An attacker can easily reconstruct these passwords and thus gain access to privileged maintenance operations. NOTE: this is different from CVE-2014-2350.

Common Vulnerability Scoring System (CVSS)

CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N
Low
Attack complexity
Local
Attack vector
None
Availability
High
Confidentiality
None
Integrity
Low
Privileges required
Unchanged
Scope
None
User interaction
5.5
Base score
1.8
3.6
Exploitability score
Impact score
 

Verification logic

 